CQ Series
| Availability: | |
|---|---|
|
| |
Data Sheet
| Parameter | CQ1KJ(S) | CQ1KH | CQ2KJ(S) | CQ2KH | CQ3KJ(S) | CQ3KH | CQ6K (S) | CQ10K (S) |
|---|---|---|---|---|---|---|---|---|
| General | ||||||||
| Phase | Single phase with earth | |||||||
| Capacity | 1000 VA / 800 W | 1000 VA / 1000 W | 2000 VA / 1600 W | 2000 VA / 2000 W | 3000 VA / 2400 W | 3000 VA / 3000 W | 6000 VA / 6000 W | 10000 VA / 10000 W |
| Input | ||||||||
| Voltage range | 110-300 VAC @60% load; 160-300 VAC @100% load | 110-300 VAC @50% load; 176-300 VAC @100% load | ||||||
| Frequency range | 40-70 Hz | |||||||
| Power factor | >=0.95 @100% load | >=0.97 @100% load | >=0.99 @100% load | |||||
| Output | ||||||||
| Output voltage | 220 VAC ±1% (208/220/230/240 V selectable on panel) | |||||||
| Voltage range (battery mode) | ±1% | |||||||
| Frequency range (sync window) | 47-53 or 57-63 Hz | |||||||
| Frequency range (battery mode) | 50 Hz ±0.25 Hz (60 Hz optional) | |||||||
| Surge ratio | 3:1 | |||||||
| Harmonic distortion | <=3% THD (linear load); <=6% THD (non-linear load) | |||||||
| Transfer time - AC to DC | 0ms | |||||||
| Transfer time - Inverter to bypass | 4 ms (under standard conditions) | |||||||
| Waveform | Pure sine wave | |||||||
| Battery | ||||||||
| Standard - Battery model | 12 V / 7 Ah | |||||||
| Standard - Quantity | 2 (optional 3) | 4 (optional 6) | 6 (optional 8) | 12 (optional 14) | 16 | |||
| Standard - Max. charge current | 1.0 A (max.) | — | 1.0A | |||||
| Standard - Charge voltage | 27.5 (41.0) VDC ±1% | 55 (82.1) VDC ±1% | 82.1 (110) VDC ±1% | 165 (192.5) VDC ±1% | 220 VDC ±1% | |||
| Long-run - Battery model | Depends on application | |||||||
| Long-run - Quantity | 3 | — | 6 | — | 8 | — | 16 | |
| Long-run - Max. charge current | 4 A | — | 4 or 8 A selectable (standard 4 A) | — | 2 or 8 A selectable (standard 4 A) | — | Adjustable 1-12 A | |
| Long-run - Charge voltage | 41.0 VDC ±1% | — | 82.1 VDC ±1% | — | 110 VDC ±1% | — | 220 VDC ±1% | |
| Display & alarms | ||||||||
| LCD/LED display | Load level, battery capacity, utility/battery/bypass mode, fault indication | |||||||
| Alarm | ||||||||
| Battery mode | One beep every 4 s | |||||||
| Battery low | One beep per second | |||||||
| Overload | One beep per second | |||||||
| Fault | Continuous beep | |||||||
| Dimensions | ||||||||
| Standard - Dimensions D×W×H (mm) | 352×145×213 | 450×192×345 | 384×192×730 (incl. wheels) | |||||
| Standard - Net weight (kg) | 8.8(10.9) | 8.8 | 19.5(23.7) | 19.5 | 23.7(27.7) | 23.7 | 40.78 | 50.1 |
| Standard - Carton dimensions D×W×H (mm) | — | 384×260×870 mm | ||||||
| Long-run - Dimensions D×W×H (mm) | 352×145×213 | — | 450×192×345 | — | 450×192×345 | — | 450×192×335 | |
| Long-run - Net weight (kg) | 5.8 | — | 23.7 | — | 27.7 | — | 9.42 | 10.4 |
| Long-run - Carton dimensions D×W×H (mm) | — | 500×318×460 mm | ||||||
| Environment | ||||||||
| Temperature & humidity | RH 20-90%, 0-40 °C (non-condensing) | |||||||
| Noise level | <50 dBA @1 m | |||||||
| Control & management | ||||||||
| Smart RS-232 | Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8, Linux, Unix | |||||||
| Optional SNMP | Power management supports SNMP and network management | |||||||
GROUP SITE
COMPANY
CONTACT US